1.
Enclosure shall be designed to be a tight fitting to the
perimeter/envelope of the equipment. A 2” clearance shall be
provided between the enclosure and the equipment on all sides
and the top.
2.
Each sound enclosure should be factory assembled and
skidded if size and scale permits. The enclosure shall be
designed to incorporate: forced air ventilation with
acoustically treated air intake for ventilation.
3.
The enclosure frame shall be made
·
of a heavy-duty aluminum square tubing frame that
allows one of each wall and roof panel to be removable without
utilizing any screws. A three directional slip fit aluminum
corner fitting piece shall be provided at each of the eight
corners to connect all aluminum frame pieces together.
·
or the panels shall be self framing with a
galvanized angle that allows one of each wall and roof panel to
be removable without demounting the structure. Enclosures over
14” clear shall have 4” structural steel spanners.
4.
Acoustical panels shall have 16 gauge galvanized steel
channel provided for bottom caps and top caps and opening.
5.
Acoustical Panels:
a.
Wall and roof panels shall have exterior skin of 16-gauge
damped galvanized steel. Skin shall be 2.5#/sq.ft.
b.
4” absorption material. 6#/cu.ft. bagged in a 2-mil
polyethylene bag and all edges of bag to be heat-sealed.
c.
22-gauge perforated galvanized steel inner liner.
6.
All doors should be provided with acoustic seals on all
four sides with galvanized, stainless steel, or nylon hinges and
handles.
7.
Acoustical seal strips provided between panels, frame,
and the floor.
8.
One each side wall panel to be easily removable via a
quick release retainer clamps.
9.
Panel Acoustical Performance shall have been tested by an
independent laboratory and achieve an STC=40 & NRC=1.0
4” Panelized Enclosure Specification
ArtUSA Steel Sound Enclosure
Specification
1.0 General
Acoustical Panel Enclosures shall
be insulated double-wall construction and shall be provided as
indicated on drawings by a recognized manufacturer with
published standards of construction and technical performance.
The manufacturer shall have produced a standard
factory-fabricated panel system and components for at least 5
years. Performance of the fabricated and installed system shall
conform to all specifications listed herein.
2.0
Materials
2.1
Acoustical Metal Panels
A.
All panels and their components shall be pre-fabricated,
sectional, all metal-clad, modular and designed for easy and
accurate field assembly. The panels and components shall not be
susceptible to damage due to extended exposure to vibration, air
temperature or humidity with the passage of time.
B. Panel
Construction
1.
All panels shall be (4) inches thick, as noted on drawings, with
a solid galvanized steel Type G90 exterior shell and a
perforated/solid galvanized steel type G90 interior shell. The
panels shall be connected together by means of a tongue and
groove connection and held together rigidly by the use of
self-drilling sheet metal screws.
2.
The panel shell framing members and internal reinforcements
shall be welded, screwed and/or riveted together to form a
metal-sheathed panel of sufficient strength for maximum
operating loads specified in the structural performance section
of these specifications.
3.
The solid exterior outer galvanized steel shell thickness shall
be 18 ga. minimum and the interior perforated galvanized steel
shell shall be 22-ga. minimum thick.
4.
Where perforated materials are indicated, all perforations shall
be 3/32" dia. holes on 3/16" staggered centers and shall result
in an open area of no less than 23 percent.
5.
All panel internal and external reinforcing members shall be
minimum 18 ga. galvanized steel.
6.
Each panel shall be filled with sound-absorbing materials that
are inert, mildew-resistant, verminproof, and incombustible.
C.
Panel Components and Installation
1.
All accessory trim items shall be of 18 ga. minimum galvanized
steel and shall be furnished in factory-standard lengths to be
field cut to specified dimensions. Location and quantity of
sheet metal screws and trim requirements shall be in accordance
with the manufacturer’s installation details.
2.
Base channel shall be installed on a level and structurally
sound surface.
3.
All external panel connectors, trim items, accessories, base
channel/panel interfaces/base channel/floor interfaces, and
other sections as noted on the drawings shall be sealed with an
acoustical sealant that shall not harden and prevent disassembly
in the future.
D. Structural
Performance
1.
Any special external panel loading conditions including wind,
snow and equipment shall be provided for as per specifications.
2.
Under the indicated loading conditions, the entire enclosure
system shall be self-supporting and/or will be supported as per
the specifications. The installer shall furnish and assemble all
structural members in strict accordance with drawings and
manufacturer’s installation details.
3.
Under the above loading conditions, the assembled acoustical
structure shall not exhibit any panel joint deflection in excess
of L/240, where L is the unsupported span length of any panel
section in the erected structure.
E.
Acoustical Performance
The
manufacturer shall provide certified testing data indicating
sound absorption and transmission loss characteristics of the
panel assembly.
F. Accessory
Items
Doors, windows, electrical systems, ventilating systems,
accessory components, etc., shall be provided in accordance with
drawings.
G. Manufacturer
All
materials shall be provided by ArtUSA Noise control Products,
Inc.
Click the Icons
Below to View Pages

Acousti-Curtain
Products |
Alum-A-Frame
Enclosures |

Modular Acoustic
Panel Enclosure |

Quick Removal
Enclosures |
|
|